The preset temperature limit (SP) should always be set to a value higher than the modulating range of the burner. Otherwise, normal modulation of the burner may cause the burner to shut off prematurely.
The maximum limit for a single line heater is not the same as the limit for a heater with a manifold. On single line heaters set the maximum limit to at least 50 degrees F above setpoint of the modulating controller. On heaters with manifolds set the limit to at least 80 degrees F above the setpoint of the modulating controller.
The setpoint (SP) is not one of the settings shown in Figure 3. The settings shown in Figure 3 do not normally require any further change after the heater is put in service.
|
Figure 3. Programming Honeywell
DC230L-EE-00-10-0A00000-20-0
high media temperature controller for Heatec HC and HCS heaters
|
|
Group Prompt
(SET UP button)
|
Function
Prompt
(FUNCTION button)
|
Value or
Selection
(up / down arrows)
|
|
Group Prompt
(SET UP button)
|
Function Prompt
(FUNCTION button)
|
Value or
Selection
(up / down arrows)
|
|
LOCK
|
SECUR
|
0
|
|
COM
|
ComSTA
|
|
|
|
LOCK
|
CAL
|
|
|
ComADR
|
|
|
|
|
|
|
|
SHDTIM
|
|
|
LIMIT
|
Lo or Hi
|
HIGH
|
|
|
PARITY
|
|
|
|
POWRUP
|
NORM
|
|
|
BAUD
|
|
|
|
SP MAX
|
500
|
|
|
TX DLY
|
|
|
|
SP MIN
|
20.00
|
|
|
UNITS
|
|
|
|
DISPLY
|
PROC
|
|
|
LOOPBK
|
|
|
|
|
|
|
|
|
|
|
INPUT1
|
DECMAL
|
8888
|
|
ALARMS
|
A1S1VA
|
|
|
|
UNITS
|
F
|
|
|
A1S2VA
|
|
|
|
IN1TYP
|
J L
|
|
|
A2S1VA
|
|
|
|
XMITR1
|
|
|
|
A2S2VA
|
|
|
|
IN1 HI
|
770
|
|
|
A1S1TY
|
NONE
|
|
|
IN1 LO
|
20.00
|
|
|
A1S2TY
|
NONE
|
|
|
BIAS 1
|
0.0
|
|
|
A2S1TY
|
NONE
|
|
|
FILTR1
|
1
|
|
|
A2S2TY
|
NONE
|
|
|
BRNOUT
|
UP
|
|
|
A1S1HL
|
|
|
|
EMIS
|
|
|
|
A1S2HL
|
|
|
|
FREQ
|
60
|
|
|
A2S1HL
|
|
|
|
DISPLY
|
|
|
|
A2S2HL
|
|
|
|
|
|
|
|
ALHYST
|
0.1
|
|
OPTIONS
|
AUXOUT
|
|
|
|
ALARM1
|
|
|
|
0 PCT
|
|
|
|
BLOCK
|
DIS
|
|
|
100 PCT
|
|
|
|
|
|
|
|
EXT RST
|
|
|
|
|
|
|