Publication No. 5-04-119

Setting Honeywell controllers
used with Heatec vertical fuel tanks

This document provides information for setting Honeywell controllers DC230B-EE-20-10-0A00000-00-0 (Figure 1) when used to indicate levels in Heatec fuel tanks. It applies to Heatec vertical fuel tanks equipped with Siemens Sitrans P, Series DSIII pressure transmitters.

The controller indicates levels of fuel in the tank. Levels are shown in feet, measured above the level where the transmitter is installed. The transmitter is installed 1.33 feet (16 inches) above the bottom of the tank. Thus, there are approximately 941 gallons of fuel in the tank when the controller indicates zero.

The controller automatically activates an alarm when the tank is 90 percent full. The controller also activates an alarm when the level is at zero.

Honeywell controllers purchased from Heatec are normally set at our factory and require no further setup. However, the controller can be reset in the field using the information shown in Figure 2.

Honeywell UDC 2300 Universal Digital Controller User Manual is furnished with each controller. Please refer to this manual for instructions on using the buttons to set the controller.

Please refer to Heatec Tec-Note, Publication 5-04-115 for more information on levels and the Siemens pressure transmitter.

<

Figure 2. Settings for Honeywell Controller DC230B-EE-20-10-0A00000-00-0 used with Heatec vertical fuel tanks.

Group Prompt

Function Prompt

Capacity (gallons) of Heatec vertical fuel tanks

6,500

13,000

20,000

23,000

TIMER

TIMER

DIS

DIS

DIS

DIS

 

 

 

 

 

 

TUNING

CYCT1 or CT1 X3

1

1

1

1

 

SECUR

0

0

0

0

 

LOCK

NONE

NONE

NONE

NONE

 

A TUNE

DIS

DIS

DIS

DIS

 

RN HLD

DIS

DIS

DIS

DIS

 

SP SEL

DIS

DIS

DIS

DIS

 

 

 

 

 

 

SPRAMP

SPRAMP

DIS

DIS

DIS

DIS

 

 

 

 

 

 

ATUNE

FUZZY

DIS

DIS

DIS

DIS

 

TUNE

DIS

DIS

DIS

DIS

 

 

 

 

 

 

ALGOR

CTRALG

ONOF

ONOF

ONOF

ONOF

 

OUTALG

RLY

RLY

RLY

RLY

 

RLY TY

MECH

MECH

MECH

MECH

 

 

 

 

 

 

INPUT1*

DECIMAL

888.8

888.8

888.8

888.8

 

UNITS

NONE

NONE

NONE

NONE

 

IN1TYP

4-20

4-20

4-20

4-20

 

XMITR1

LIN

LIN

LIN

LIN

 

IN1 HI

40.00

40.00

40.00

40.00

 

IN1 LO

0.00

0.00

0.00

0.00

 

RATIO1

1.0

1.0

1.0

1.0

 

BIAS 1

0.0

0.0

0.0

0.0

 

FILTR1

1

1

1

1

 

BRNOUT

NONE

NONE

NONE

NONE

 

FREQ

60

60

60

60

 

DISPLY

PR N

PR N

PR N

PR N

 

LNGUAG

ENGL

ENGL

ENGL

ENGL

 

 

 

 

 

 

CONTRL

LSP’S

ONE

ONE

ONE

ONE

 

SP TRK

NONE

NONE

NONE

NONE

 

PWR UP

ALSP